© Microsoft © SIEMENS
To exploit completely advantages
of Actuator Organizer or AI Organizer the I/Os must be
labeled according
appropriate
rules, which are integrated in algorithm assigning I/Os to STEP 7 FC block at
their calls. Symbol name for
I/O is
combined with two parts. Leading part is the actuator name and second part is
an extension according to
the meaning
of I/O. Meaning of I/Os and their
extensions are described in the table bellow.
Form of I/O label MUST BE KEPT !
1-st letter |
|
D |
Density |
E |
Electrical values (current,tension, power ...) |
F |
Flow |
G |
Position, length |
H |
Weight |
L |
Level |
M |
Humidity |
P |
Pressure |
Q |
Analyzaa of medium |
R |
Radioaktivity, radiation |
S |
Speed, frequency |
T |
Temperature |
V |
Viscosity |
W |
Mechanical power, weight |
X |
The other values |
Y |
Vibration |
2-nd letter |
|
I |
Analog input to PLC |
O |
Analog output to PLC |
X |
Digital input to PLC |
Y |
Digital output to PLC |
Signals for acctuators ( DI, DO )
1-st letter |
|
Q |
Status |
C |
Status from frequency converter |
K |
Order |
H |
Signalization of status or non standart function |
L |
Operator order from the local control box |
Meaning of I/O signal
2-nd letter |
|
A |
Up |
B
|
Down / Backward |
C |
Mode computer |
D
|
Local mode |
E
|
Release |
F
|
Failure |
G |
Position, length |
H |
Maximum |
J
|
Control voltage |
L |
Minimum |
M |
Reset |
N |
Emergency stop |
O
|
Overload |
P
|
Turns , frequency |
R
|
Ready |
S
|
Services switch |
T
|
Open, opened |
U
|
Close, closed |
V
|
Off / STOP |
W
|
Setpoint |
Z
|
On / Start / Forward |
Example
:
DO order Open DI Opened DI
Closed Local control
V101_KT V101_QT V101_QU V101_QD
DO order Start DI Running DI control volt.OK DI
motor protection
M102_KZ M102_QZ M102_QJ* M102_QF *
* - logical 0 ... Motor
protection is active, motor is switched OFF, FAULTY state
- logical 1 ... Motor protection is OK. Motor is running. Normal
state. Control voltage is ON.